The Impact Of Demagnetization On The Generator Itself

Jun 18, 2025

Leave a message

1. Due to the occurrence of slip after engine demagnetization, a differential frequency current occurs in the generator rotor circuit, causing losses in the rotor circuit. If the differential frequency current exceeds the allowable value, it will cause the rotor to overheat. Especially for high power rate large units with direct cooling, their thermal capacity margin is relatively reduced, and the rotor is more prone to overheating. The differential frequency current on the surface of the rotor may also cause severe local overheating or even burns on the contact surfaces of the rotor body slot wedges and protective rings.
2. After the demagnetization generator enters asynchronous operation, the equivalent reactance of the generator decreases and absorbs reactive power from the power system. The larger the active power carried before demagnetization, the greater the slip, the smaller the equivalent reactance, and the greater the absorbed reactive power. After demagnetization under heavy load, the generator stator will overheat due to overcurrent.
3. For large steam turbine generators with direct cooling and high power rates, the maximum value of the average asynchronous torque is relatively small, and the inertia constant is also relatively reduced. The rotor also shows a significant asymmetry in the longitudinal and transverse axes. Due to these reasons, after demagnetization under heavy loads, the torque and active power of this generator will experience severe periodic oscillations. For hydro generators, due to the small maximum average asynchronous torque and the asymmetry of the rotor in the longitudinal and transverse axes, similar situations will also occur during demagnetization operation under heavy loads. In this case, a large or even exceeding rated motor torque will periodically act on the shaft system of the generator and be transmitted to the machine base through the stator. At this time, the slip also undergoes periodic changes, and its maximum value may reach 4% to 5%, causing the generator to periodically overspeed severely. These situations directly threaten the safety of the crew.
4. During demagnetization operation, the leakage of magnetic flux at the end of the stator is enhanced, which will cause overheating of the end components and edge iron cores.

 

Send Inquiry